Feature |
1. Fire prevention foam pad depth 50T + Thermal expansion tape thickness 2T.
2. Provides excellent fire prevention for contraction/expansion. 3. Semi-permanent elastic body that absorbs all external shock. 4. Can be installed easily due to elastic material. 5. Provides excellent soundproofing. 6. Applied to steel pipe less than 100A. 7. Applied to penetration sleeve less than 150A. 8. Components : Fireproof Filling Compound+Fire Prevention Sealant+Thermal Insulation Material. |
---|
Pipe size, location, and type | 100A Floor Steel Pipe | Pipe size, location, and type | 100A Wall Steel Pipe |
---|---|---|---|
Filling material | AG-ST110 (50mm) | Filling material | AG-ST110 (50mm) |
Fire prevention sealant | AG-1119 thickness 3T | Fire prevention sealant | AG-ST119 thickness on both sides 3T |
Thermal insulation material | AG-400(25t*200mm) | Thermal insulation material | AG-400(25t*200mm) |
Location of construction | One-side top construction | Location of construction | Double-sided construction |
Structure grade | C-2 (Lightweight foam concrete wall for 2 hours) | Structure grade | A-2 (Lightweight Steel Structural Walls for 2 hours) |
Feature |
1. Fire prevention foam pad depth 75T + Thermal expansion tape thickness 2T.
2. Provides excellent fire prevention for contraction/expansion. 3. Semi-permanent elastic body that absorbs all external shock. 4. Can be installed easily due to elastic material. 5. Provides excellent soundproofing. 6. Applied to steel pipe more than 125A, 150A. 7. Applied to penetration sleeve more than 200A. 8. Components : Fireproof Filling Compound+Fire Prevention Sealant+Thermal Insulation Material. |
---|
Pipe size, location, and type | 150A floor steel pipe | Pipe size, location, and type | 150A wall steel pipe |
---|---|---|---|
Filling material | AG-ST120(75mm) | Filling material | AG-ST100(50mm) |
Fire prevention sealant | AG-1119 thickness 3T | Fire prevention sealant | AG-1119 thickness on both sides 3T |
Thermal insulation material | AG-400(25t*400mm) | Thermal insulation material | AG-400(25t*300mm) |
Location of construction | One-sided top construction | Location of construction | Double-sided construction |
Structure grade | C-2 (Lightweight foam concrete wall for 2 hours) | Structure grade | C-2 (Lightweight foam concrete wall for 2 hours) |
Feature |
1. Fire prevention foam pad depth 50T + Thermal expansion tape thickness 5T.
2. Provides excellent fire prevention for contraction/expansion. 3. Semi-permanent elastic body that absorbs all external shock. 4. Can be installed easily due to elastic material. 5. Provides excellent soundproofing. 6. Applied to steel pipe more than 200A. 7. Applied to penetration sleeve more than 200A. 8. Components : Fireproof Filling Compound+Fire Prevention Sealant+Thermal Insulation Material |
---|
Pipe size, location, and type | 400A floor steel pipe | Pipe size, location, and type | 400A wall steel pipe |
---|---|---|---|
Filling material | AG-ST130(50mm) | Filling material | AG-ST230(50mm) filling on both sides |
Fire prevention sealant | AG-1119 thickness 3T | Fire prevention sealant | AG-1119 thickness on both sides 3T |
Thermal insulation material | AG-400 (bottom 25T*400mm 2 layers) / (top 25T*400mm 1 layers) | Thermal insulation material | AG-400(38T*400mm) |
Location of construction | Top construction | Location of construction | Double-sided construction |
Structure grade | C-2 (Lightweight foam concrete wall for 2 hours) | Structure grade | A-2 (Lightweight Steel Structural Walls for 2 hours) |
Feature |
1. Fire prevention foam pad depth 50T + Thermal expansion tape thickness 11T.
2. Provides excellent fire prevention for contraction/expansion. 3. Semi-permanent elastic body that absorbs all external shock. 4. Can be installed easily due to elastic material. 5. Foamed 20-30 times in the event of fire. (penetration part is sealed) 6. Provides excellent soundproofing. 7. Applied to PVC pipe less than 200A. (to be tested for 300A) 8. Components : Fireproof Filling Compound+Fire prevention sealant. |
---|
Pipe size, location, and type | 100A floor PVC | Pipe size, location, and type | 150A floor PVC |
---|---|---|---|
Filling material | AG-PF210(50mm) | Filling material | AG-PF210(50mm) |
Fire prevention sealant | AG-1119 thickness 3T | Fire prevention sealant | AG-1119 thickness on both sides 3T |
Thermal insulation material | X | Thermal insulation material | X |
Location of construction | One-sided top construction | Location of construction | One-sided top construction |
Structure grade | C-2 (Lightweight foam concrete wall for 2 hours) | Structure grade | C-2 (Lightweight foam concrete wall for 2 hours) |
Pipe size, location, and type/th> | 200A floor PVC | Pipe size, location, and type | 300A floor PVC (To be tested) |
---|---|---|---|
Filling material | AG-PF210(50mm) | Filling material | (To be tested) |
Fire prevention sealant | AG-1119 thickness 3T | Fire prevention sealant | (To be tested) |
Thermal insulation material | X | Thermal insulation material | (To be tested) |
Location of construction | Top and bottom construction | Location of construction | (To be tested) |
Structure grade | C-2 (Lightweight foam concrete wall for 2 hours) | Structure grade | (To be tested) |
Feature |
1. Fire prevention foam pad depth 75T+Thermal expansion tape 6T.
2. Provides excellent fire prevention for contraction/expansion. 3. Semi-permanent elastic body that absorbs all external shock. 4. Can be installed easily due to elastic material. 5. Foamed 20-30 times in the event of fire. (penetration part is sealed) 6. Provides excellent soundproofing. 7. Applied to PVC pipe less than 100A. 8. Components : Fireproof Filling Compound+Fire Prevention Sealant. |
---|
Feature |
1. Fire prevention foam pad depth 75T+Thermal expansion tape 6T.
2. Provides excellent fire prevention for contraction/expansion. 3. Semi-permanent elastic body that absorbs all external shock. 4. Can be installed easily due to elastic material. 5. Foamed 20-30 times in the event of fire. (penetration part is sealed) 6. Provides excellent soundproofing 7. Applied to PVC pipe less than 200A. (to be tested for 300A) 8. Components : Fireproof Filling Compound+Fire Prevention Sealant |
---|
Pipe size, location, and type | 100A wall PVC | Pipe size, location, and type | 200A wall PVC |
---|---|---|---|
Filling material | AG-PW230(50mm) | Filling material | AG-PW210(50mm) |
Fire prevention sealant | X | Fire prevention sealant | AG-1119 thickness on both sides 3T |
Thermal insulation material | X | Thermal insulation material | X |
Location of construction | One-sided construction | Location of construction | Double-sided construction |
Structure grade | A-2(Lightweight Steel Structural Walls for 2 hours) | Structure grade | A-2(Lightweight Steel Structural Walls for 2 hours) |
Feature |
1. Main ingredient of fireproof filling compound structure for facility¡¯s penetration part, used in various specifications.
2. Provides consistent expansion performance in the event of fire with advanced technical skills and high quality. 3. Expands up to 30 times in the event of fire to prevent flame, smoke, and gas by sealing the penetration part tightly. 4. Maintains excellent durability under various circumstances. |
---|
Pipe size, location, and type | 100A floor steel pipe (after heat insulation) | Pipe size, location, and type | 200A floor steel pipe (after heat insulation) |
---|---|---|---|
Filling material | AG-200 (expansion tape thickness 5T+depth 50mm) | Filling material | AG-200 (expansion tape thickness 6T+depth 75mm) |
Fire prevention sealant | AG-1119 thickness 3T | Fire prevention sealant | AG-1119 thickness 3T |
Thermal insulation material | AG-400(25t*200mm) | Thermal insulation material | AG-400(25t*400mm) |
Location of construction | One-sided top construction | Location of construction | One-sided top construction |
Structure grade | C-2(Lightweight foam concrete wall for 2 hours) | Structure grade | C-2(Lightweight foam concrete wall for 2 hours) |
Pipe size, location, and type | 400A floor steel pipe (after heat insulation) | Pipe size, location, and type | 200A floor steel pipe (after heat insulation) |
---|---|---|---|
Filling material | AG-200 (expansion tape thickness 10T+depth 100mm) | Filling material | AG-200 (expansion tape thickness 5T+depth 50mm) |
Fire prevention sealant | AG-1119 thickness 3T | Fire prevention sealant | AG-1119 thickness 3T |
Thermal insulation material | AG-400 (bottom 38t*400mm, top 25t*400mm) | Thermal insulation material | AG-400 (25t*400mm) |
Location of construction | One-sided top construction | Location of construction | Double-sided construction |
Structure grade | C-2 (Lightweight foam concrete wall for 2 hours) | Structure grade | A-2 (Lightweight Steel Structural Walls for 2 hours) |
Pipe size, location, and type | 200A wall steel pipe (after heat insulation) | Pipe size, location, and type | 400A wall steel pipe (after heat insulation) |
---|---|---|---|
Filling material | AG-200(6t*75mm) | Filling material | AG-200(10t*50mm) |
Fire prevention sealant | AG-1119 thickness on both sides 3T | Fire prevention sealant | AG-1119 thickness on both sides 3T |
Thermal insulation material | AG-400(25t*300mm) | Thermal insulation material | AG-400(25t*400mm) |
Location of construction | Double-sided construction | Location of construction | Double-sided construction |
Location of construction | A-2 (Lightweight Steel Structural Walls for 2 hours) | Location of construction | A-2 (Lightweight Steel Structural Walls for 2 hours) |
Structure of facility¡¯s penetration part | Sleeve specification | Filling material model name | AAG-200 specification (applied thickness) |
---|---|---|---|
Metallic pipe floor | 150A less than | ST110 | 2T |
Metallic pipe floor | 200A | ST120 | 2T |
Metallic pipe floor | AG-400(25t*400mm) | ST130 | 5T |
Metallic pipe floor(fixture) | 150A less than | ST1100 | 5T |
Metallic pipe wall | 250A more than | ST230 | 5T |
PVC pipe floor | 125A less than | PF210 | 10T |
PVC pipe floor | 150A more than | PF210 | 18T |
PVC pipe floor(fixture) | 125A less than | PF2200 | 10T |
PVC pipe wall | 125A less than | PW230 | 5T |
PVC pipe wall | 150A more than | PW210 | 18T |
After heat insulation | - | AG200 | 5T |